  MTC600 Datasheet HTML 1Page - Emerson Network Power MTC600 Datasheet HTML 2Page - Emerson Network Power MTC600 Datasheet HTML 3Page - Emerson Network Power MTC600 Datasheet HTML 4Page - Emerson Network Power MTC600 Datasheet HTML 5Page - Emerson Network Power MTC600 Datasheet HTML 6Page - Emerson Network Power MTC600 Datasheet HTML 7Page - Emerson Network Power MTC600 Datasheet HTML 8Page - Emerson Network Power MTC600 Datasheet HTML 9Page - Emerson Network Power Next Button
Zoom Inzoom in Zoom Outzoom out
 3 / 19 page
background image
Rev. 05.26.08
MTC600 Series
3 of 19
Embedded Power for
Business-Critical Continuity
Electrical Specifications
Input
-48 Vdc Models
Input Range (Operating)
-39.5 to -72 Vdc
Supports -48 V and -60 V battery plants
Input Range (Non-operating)
0 to -39.5 Vdc
-72 to -75 Vdc
Power Module may or may not operate in part
of this range, but will not be damaged
Input Fusing
Internal 24 A Fuses
In both A & B feeds and A & B return lines
Input ORing
Internal
In both A & B feeds and A & B return lines
Inrush Current
≤80 A
For t < 1 ms
Input Current
12.8 A
18.2 A
Typical with 600 W out, -54.0 Vin
Maximum with 600 W out, -39.5 Vin
Holdup Time
5 ms
7 ms
10 ms
10 ms
Minimum at 600 W with one PM
Typical at 600 W with one PM
Typical at 400 W with one PM
Minimum at 600 W with two PMs
UnderVoltage Lockout
39.5 ±1.0 V
37.0 ±1.0 V
Turn-On voltage
Turn-Off voltage
Reverse Polarity Protection
Included
Protected against reverse polarity over
magnitude of specified input range
AC Models
Input Range (Operating)
90 to 264 Vac
Supports typical worldwide single-phase inputs
Input Range (Non-operating)
0 to 90 Vac
264 to 282 Vac
Power Module may or may not be operating in
part of this range, but will not be damaged
Frequency
47 to 63 Hz
Input Fusing
Internal 15 A Fuses
Inrush Current
≤45 A
I2t integral compatible with 15 A fast-blow fuse
Power Factor
0.99 typical
Meets EN61000-3-2
Harmonics
<2.30 Arms (odd)
<1.08 Arms (even)
Input Current
2.95 A
6.6 A
Typical with 600 W out, 230 Vac
Maximum with 600 W out, 110 Vac
Holdup Time
16.7 ms
20 ms
At 110 Vac, 60 Hz
At 230 Vac, 50 Hz
UnderVoltage Lockout
87 ± 2.5 V
83 ± 2.5 V
Turn-On voltage
Turn-off voltage
OverVoltage Lockout
282 Vac
Power Module will turn-off if input voltage
exceeds this voltage and not turn on
until input voltage is reduced below this level



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19


Folha de dados Download

Go To PDF Page


Ligação URL



ALLDATASHEET é útil para você?  [ DONATE ] 

Sobre Alldatasheet   |   Publicidade   |   Contato conosco   |   Privacy Policy   |   Link para a ficha técnica    |   roca de Link   |   Lista de Fabricantes
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com