FLM-4WB-R
AI

The **FLM-4WB-R** is a specialized electronic module manufactured by **Bosch**, primarily used in fire alarm systems. It functions as a **Field Loop Module (FLM)** designed to monitor and interface conventional 4-wire smoke detectors with a digital addressable fire alarm loop.
---
## 1. Technical Specifications
The following table outlines the core electrical and mechanical characteristics of the FLM-4WB-R:
| Feature | Specification |
| :--- | :--- |
| **Input Voltage (LSN)** | 15 V DC to 33 V DC |
| **External Power Supply** | 24 V DC (nominal) |
| **Max. Current Consumption** | Approx. 0.1 mA (on LSN loop) |
| **EOL Resistance** | 3.9 kΩ (standard) |
| **Protection Class** | IP 30 |
| **Housing Material** | ABS Plastic (Flame retardant) |
---
## 2. Key Electronic Components & Functions
### A. LSN Interface (Local Security Network)
The module acts as a bridge between the **LSN bus** (the "brain" of the fire panel) and conventional detectors. It contains integrated circuits (ICs) that handle:
* **Addressing:** Unique identification of the module on the loop.
* **Data Transmission:** Sending status updates (Alarm, Trouble, Normal) back to the control panel.
### B. Relay Outputs (Power Reset)
Since 4-wire smoke detectors require a constant power source, they must be "reset" by momentarily cutting power after an alarm. The FLM-4WB-R includes an **integrated relay** that:
* Interrupts the 24V power supply to the detectors upon a reset command from the panel.
* Ensures the sensors are cleared of smoke particles and ready for re-activation.
### C. Monitoring Circuitry
The module monitors the conventional line for two specific electrical states:
1. **Alarm State:** Detected by a drop in resistance/increase in current when a detector triggers.
2. **Trouble State:** Detected via the **End-of-Line (EOL)** resistor. If a wire is cut, the module senses an open circuit and reports a fault.
---
## 3. Wiring Configuration
The "4WB" in the model name refers to **4-Wire Bus/Branching**. Below is the typical connectivity logic:
```mermaid
graph TD
A[Fire Alarm Panel - LSN] -->|Data + Power| B(FLM-4WB-R)
C[External 24V DC PS] -->|Power| B
B -->|4-Wire Line| D[Conventional Detector 1]
D -->|4-Wire Line| E[Conventional Detector 2]
E -->|Terminator| F[EOL Resistor 3.9k]
```
---
## 4. Key Advantages
* **Retrofitting:** Allows old conventional 4-wire detectors to work with modern digital Bosch panels.
* **Isolation:** Usually features integrated short-circuit isolators to maintain loop integrity if a wire is damaged.
* **LED Feedback:** Includes a red LED indicator that flashes to indicate communication or stays solid to indicate an alarm state.
- ⤷
What is the difference between the FLM-4WB-R and a standard 2-wire monitor module?
- ⤷
How do you address this module using the rotary switches?
- ⤷
What are the specific wiring requirements for the EOL resistor in this module?