AI

The **8536SCO2V02S** is a specific model of a NEMA-rated magnetic motor starter manufactured by **Schneider Electric (Square D)**. It is part of the Type S product line, designed for across-the-line starting of polyphase motors.
---
## 1. Technical Specifications Breakdown
| Component | Specification Details |
| :--- | :--- |
| **Product Type** | NEMA Magnetic Motor Starter |
| **NEMA Size** | Size 1 |
| **Continuous Ampere Rating** | 27 Amperes |
| **Phase / Poles** | 3-Phase, 3-Pole |
| **Coil Voltage (V02)** | 120V AC @ 60 Hz / 110V AC @ 50 Hz |
| **Control Circuit (S)** | Separate Control Circuit (Commonly used with external power) |
| **Enclosure Type** | Open (No metal box/cover included) |
| **Overload Relay** | Melting Alloy (Thermal) |
---
## 2. Key Electronic & Electromechanical Parts
The unit is comprised of three primary sections that work together to control and protect the motor.
### A. The Magnetic Contactor
The heart of the device is the contactor. When the **120V coil** is energized, it creates a magnetic field that pulls the power contacts closed, allowing 3-phase power to flow to the motor.
* **Contacts:** High-conductivity silver cadmium oxide contacts designed to resist welding and arc erosion.
* **Coil (V02):** The electromagnetic actuator. The "V02" code signifies the specific 120V AC winding.
### B. Thermal Overload Relay (Melting Alloy)
This part protects the motor from overheating due to excessive current draw.
* **Thermal Units:** It requires "Heater Elements" (B-Series) which must be sized according to the motor's Full Load Amps (FLA).
* **Mechanism:** If the current stays too high for too long, the heat melts a low-temperature solder inside the heater, releasing a spring-loaded mechanism that opens the control circuit and shuts down the starter.
### C. The "S" Feature (Separate Control)
The "S" at the end of the model number indicates that the starter is configured for a **Separate Control Circuit**.
* Unlike "Common Control" (where the coil pulls power directly from the motor lines), this version allows the control logic (Start/Stop buttons, PLCs) to run on a separate, usually lower-voltage power source (120V), independent of the main 480V or 600V motor power.
---
## 3. Dimensions and Mounting
| Feature | Measurement |
| :--- | :--- |
| **Height** | 6.77 inches (172 mm) |
| **Width** | 3.50 inches (89 mm) |
| **Depth** | 4.21 inches (107 mm) |
| **Mounting** | Surface mount (Panel) |
---
## 4. Horsepower (HP) Ratings
Depending on the line voltage supplied to the motor, the 8536SCO2V02S is rated as follows:
* **200V / 230V AC:** 7.5 HP
* **460V / 575V AC:** 10 HP
---
- ⤷
Which specific B-series heater elements are required for a 5HP 230V motor?
- ⤷ How do I wire the separate control circuit (S suffix) to a 24V PLC?
- ⤷ What is the difference between an 'Open' type and an 'NEMA 1' enclosure for this starter?